• long8 - 龙8 - 龙八(国际)游戏官方网站

    TransformerHigh voltage cabinetLow voltage cabinetOutdoor complete equipment

    European New Energy Special Box Change

    Hotline:+86-570-4982909 销售热线:+86-570-4982880
    Description
    Feature
    Parameter
    YB series pre installed high/low voltage substations are power equipment composed of high-voltage power equipment, distribution transformers, low-voltage power equipment, energy metering devices, and power factor compensation devices. As equipment for power supply and distribution, they have the characteristics of convenient installation and simple operation.
    Product technical features:
    1. Has 4 national invention patents, and the product technology is at the leading level in China;
    2. Rated voltage: 12-24kV;
    3. Rated frequency: 50Hz;
    4. Transformer capacity ≤ 6300KVA;
    5. The highest altitude is 4500 meters;
    6. Shell protection level: IP54;
    7. High voltage switchgear can adopt environmentally friendly gas, air insulation, SF6 gas insulation, solid insulation, and other types;
    8. The backend monitoring system can achieve online monitoring of product key points (online temperature of primary contacts, partial discharge of insulation components, and arc light);
    9. As distribution control and protection equipment for new energy generation systems such as photovoltaic and wind power;
    10. Normal service life: 20 years;

    Project Name

    Unit

    HVElectricalApparatus

    Transformer

    IMElertrical Anpparatus

    Rated voltage

    kV

    6;12

    6/0.4;10/0.4

    0.4

    Rated capacity

    kVA

    1200~1250

    Ⅱ 50~400

    Rated current

    A

    630,800,1250

    200~2000

    Rated breaking current

    A

    Load switch 630A

    15~63

    kA

    The combination of electrical appliances depends on the fuse

    Rated short time withstand current

    kA

    20 kA

    200~400kVA

    15×1

    25 kA

    >400kVA

    30×1

    Rated peak withstand current

    kA

    31.5;50

    200~400kVA

    >400kVA

    30
    60

    Rated making current

    kA

    31.5:50

    Power frequency withstand voltage

    kV

    Phase to ground and phase to phase 42

    Oil immersed 35

    ≤300V;2

    Isolated South Fracture 48

    Dry 35

    >300V;2.5

    Lightning impulse withstand voltage (peak)

    kV

    Phase to ground and phase to phase 75

    75

    Isolation fracture 85

    Cabinet protection level

    IP3X

    IP2X

    IP30

    Level of noise

    dB

    Oil immersed<55

    Dry<65


    Notes: When transformer capacity is less than 200kVA, items 5, 6 is not required.



    Copyright © 2024 KERUN INTELLIGENT CONTROL CO.LTD. All rights reserved.

    友情链接: