• long8 - 龙8 - 龙八(国际)游戏官方网站

    TransformerHigh voltage cabinetLow voltage cabinetOutdoor complete equipment

    KRSIS

    PRODUCT PARAMETERS
    1. Cold rolled steel plate or angle steel (used for welding cabinets);
    2. Aluminum zinc coated steel plate or galvanized steel plate (used for assembling cabinets);
    3. Stainless steel plate (non magnetic); cabinet
    4. Aluminum plate (non magnetic).

    Hotline:+86-570-4982909 销售热线:+86-570-4982880
    Description
    Feature
    Parameter
    The KRSIS-12V solid insulation switchgear adopts a modular structure design, which allows for arbitrary combination and expansion of the switchgear, making it convenient for maintenance and repair. Fully insulated, fully sealed, and maintenance free, all live parts are fully insulated. Adopting fully insulated busbar, longitudinally arranged, convenient and reliable connection. Equipped with an independent low-voltage room, which can be equipped with microcomputer protection and various meters, there is no need to install a low-voltage compartment on the top of the cabinet, making the arrangement of the switchgear more beautiful and compact. Equipped with an independent low-voltage room, which can be equipped with microcomputer protection and various meters, there is no need to install a low-voltage compartment on the top of the cabinet, making the arrangement of the switchgear more beautiful and compact.
    Product technical features:
    1. Adopting heat shrink insulation materials and epoxy coating insulation process, optimizing electrode shape, compact cabinet structure, and reducing floor area;
    2. The switchgear cabinet body is made of high-quality cold-rolled steel, which is formed by CNC sheet metal processing and connected by high-strength bolts and nuts and rivet nuts. The surface of the components is sprayed with plastic or galvanized technology;
    3. It can be matched with domestic ZN85-40.5 vacuum circuit breakers and foreign SF1, SF2, and FP system sulfur hexafluoride circuit breakers to meet the needs of different users;
    4. Each functional compartment of the switchgear is sealed with metal plates and equipped with independent pressure release channels;
    5. Circuit breakers, grounding switches, and other operations can be carried out when the switchgear is closed, achieving door closing operation;
    6. The structural adaptability of the switchgear is strong, with over 198 main wiring schemes that can meet the needs of different users;
    7. There is a mechanical interlocking device between the handcart, circuit breaker, grounding switch, and rear cabinet door to prevent misoperation. The "five prevention" functions are complete, safe and reliable

    Project Name

    Unit

    Product Category

    Load switch

    Combined electricalswitch

    Breaker

    lsolation switch

    Rated voltage

    kv

    12

    12

    12

    12

    Arc extinguishing type

    -

    vacuum

    vacuum

    vacuum

    -

    Rated current

    A

    630

    125

    630

    630

    Rated frequency

    Hz

    50

    50

    50

    50

    Main circuit resistance

    μΩ

    ≤150

    Note1

    ≤500

    ≤150

    ≤150

    Imin power frequency withstand voltage is the same, with phase to ground/fracture

    kv

    42/48

    42/48

    42/48

    42/48

    Same lightning impulse withstand voltage, phase to ground/fracture

    kv

    75/85

    75/85

    75/85

    75/85

    Rated short-circuit breaking current

    kA

    -

    Note2

    315

    20

    -

    Rated short-circuit making current

    kA

    50

    Note2

    80

    50

    -

    Rated short time withstand current

    kA/s

    20/4

    -

    20/4

    -

    Rated peak withstand current

    kA

    50

    Note2

    80

    50

    -

    Rated cable charging breaking current

    A

    10

    -

    -

    -

    5% rated active load breaking current

    A

    315

    -

    -

    -

    Transfer current

    A

    -

    3150

    -

    -

    Average closing speed

    m/s

    09±0.2

    -

    Average opening speed

    m/s

    13±0.2

    -

    Different periods of opening and closing

    m/s

    ≤2

    -

    Closing time

    m/s

    25~60

    -

    Opening time

    ms

    17~45

    -

    Closing bounce time

    ms

    ≤2

    -

    Mechanical life

    Load switch/circuit breaker: 10000; Isolation and grounding switch: 3000

    Protection level

    IP67

    Partial discharge value

    Pc

    Note2

    ≤5


    Note 1 in the above table: Use conductive rods instead of high-voltage fuses; Note 2: According to the high-voltage fuse; Note 3: All epoxy insulators

    Copyright © 2025 KERUN INTELLIGENT CONTROL CO.LTD. All rights reserved.

    友情链接: